RELIABLE FILTRATION
of High Turbidity water
without chemicals.
For Potable water
treatment
Recycling grey water, and sewage
Micro
100E- 12v dc power with UV disinfection 800+ litres/day
Micro100M- emergency
water,
hand operated,
40+litre/hour
Micro 150
packages 2000 to 20,000 litres/day to suit application.
OEM modules
Micro 100 module, 40+ l/hour
Micro 150 module 100+ l/hour
Incorporating Zena membranes.
www.zena-membranes.cz
Other 150E arrangements.
Septic
tank retrofit.
RO addition.
|
TYPICAL
"PACKAGE' COMPONENTS.
1. 150 modules (10
bundles/moduel, nominal 100 litres/hour)
2. low pressure blower.
3.PLC (not shown)
4. Membrane flow rate control valve , amount of bypass sets
optimum rate through membranes.
5. Low vacuum switch, used
to activate alarm, or can be used to initiate backflush.
6.Vacuum gauge, used
for setting flow and observing membrane resistance to flow.
7. Primary pump,
withdraws treated water from hollow centres of the membrane fibres. Pump shown as single helical screw,
select for constant flow at varying head, and good suction/priming
capacity. |
Helical screw
pump has additional feature that resists reverse flow during backflush.
8.Ultra violet disinfection. Used for protection against virus.
Works effectively in clear water produced from membrane.
9. Flow Meter
10. Backflush solenoid valve. during PLC controlled timed
backflush, this valve is opened. Pump 7 is stopped and pump 11 is
activated.
11. Backflush pump.
periodic operation pumps clear water into the hollow fibre membranes to
lift dirt from the fibre wall pores. Circulation of raw water caused by
air bubbles removes dirt from fibre walls. |

|